Ministry of Coal Industry of the People's Republic of China, approved on December 30, 1997, and implemented on June 1, 1998.
1 Scope
This standard specifies the requirements for automatic spray control valves used in coal mine hydraulic supports, including testing methods, inspection rules, marking, packaging, transportation, and storage. It applies to various types of automatic spray control valves installed on coal mine hydraulic supports.
2 Reference Standards
The following standards contain provisions that, through reference in this standard, constitute provisions of this standard. At the time of publication, the editions indicated were valid. All standards are subject to revision, and parties using this standard should explore the possibility of using the latest version of the standard.
3 Definitions
This standard uses the following definitions:
4 Requirements
Control valves must comply with the provisions of this standard and be manufactured according to the drawings and technical documents approved by the prescribed procedures.
4.1 Ambient Temperature
Normal operation under ambient temperatures ranging from 4°C to 40°C.
4.2 Appearance
The surface should be smooth and have an anti-corrosion protective layer that is uniform, without flaking or scratches. There should be no deformation, cracking, corrosion, or mechanical damage. The water inlet, outlet, and working fluid inlet should be clearly marked. The nameplate should be securely installed and legible.
4.3 Interface
The inlet, outlet, and working fluid inlet interfaces should be quick connectors. Their size and surface roughness should meet the requirements specified in Appendix A of this standard. After testing, there should be no leakage at the interface.
4.4 Strength
The control valve is rated for a fluid pressure of 32 MPa. It should be tested at 1.5 times the rated working pressure at the inlet for 5 minutes without any leakage, and the shell and parts should not deform or sustain damage.
4.5 Resistance Loss
When water flows through the control valve at a rate of 20 L/min, the pressure difference between the inlet and outlet ports should not exceed 0.1 MPa.
4.6 Opening Pressure
The opening pressure should not exceed 2 MPa when the water pressure is within the range of 1.0 to 7.0 MPa.
4.7 Operating Water Pressure
The control valve should be able to open and close normally when the operating water pressure is within the range of 1.0 to 7.0 MPa. During the test, it should not exhibit any automatic opening or closing phenomenon.
4.8 Service Life
After 4,000 cycles, the seal should still meet the requirements outlined in section 4.9.
4.9 Sealing
According to Table 1, the sealing test should show no pressure drop. After a 2-hour regulator test under the working fluid rated pressure and operating water pressure range, the working fluid should not experience any pressure loss.
5 Test Methods
5.1 Test System
The test system is shown in Figure 1.
5.2 Test Equipment and Tools
5.3 Test Conditions
5.4 Test Items and Methods
Table 1 outlines the test items and methods for the control valve.
Table 1: Control Valve Test Items and Methods
Serial Number | Test Item | Test Method |
---|---|---|
1 | Ambient Temperature | Test under ambient temperature of 4°C to 40°C. |
2 | Appearance | Visual inspection. |
3 | Interface | Connect the control valve to the test system, supply water to the working fluid inlet for 2 minutes, and observe for seepage or leakage. |
4 | Strength | Apply pressure at 1.5 times the rated working pressure at the inlet for 5 minutes. |
5 | Resistance Loss | Open the control valve and measure the pressure difference between the inlet and outlet at a flow rate of 20 L/min. |
6 | Opening Pressure | Adjust the water pressure to 1.0–7.0 MPa and the working fluid pressure to 0.1 MPa below, then gradually increase the working fluid pressure until the control valve opens, recording the highest pressure gauge reading. Perform five tests for each pressure level. |
7 | Operating Water Pressure | Adjust the water pressure to 1.0–7.0 MPa and open/close the control valve for 5 minutes. Conduct five continuous tests for each pressure level. |
8 | Life Test | Adjust the working fluid pressure to 5–6 MPa and the water pressure to 1.5–2.0 MPa, then cycle the control valve open and close 4,000 times. |
9 | Seal | (1) After completing the life test (not required for factory inspection); (2) The working fluid should show no pressure drop after a 2-hour test under rated working fluid pressure and operating water pressure. |
1/4 Pneumatic Fittings,Smc Pneumatic Fittings,Push To Connect Pneumatic Fittings,Airtac Pneumatic Fittings
ShinYee (Zhejiang) Pneumatic Technology Co., LTD , https://www.pneuvalve.com